EE - Power Systems

Quiz by Florenzo Miguel Aclan (Florencii)

Our brand new solo games combine with your quiz, on the same screen

Correct quiz answers unlock more play!

New Quizalize solo game modes
30 questions
Show answers
  • Q1
    For a single line to ground fault the zero sequence current is given by j3.0 pu. The current carried by the neutral during the fault is,
    j 6 pu
    j 9 pu
    j 1 pu
    j 3 pu
    30s
  • Q2
    The per unit value of a 2 ohm resistor at 100 MVA base and 10 KV base voltage is,
    2 pu
    0.5 pu
    0.2 pu
    4 pu
    30s
  • Q3
    The line currents in amperes in phases a, b and c respectively are 500 +j150, 100-j600 and -300+ j600. Determine the zero-sequence component of phase a current.
    -100 + j50 amps
    100 - j50 amps
    100 + j50 amps
    -100 - j50 amps
    30s
  • Q4
    Two-wattmeter method is applied to a 3-phase motor running at full-load. Two wattmeters indicate 85.5 kW and 34.7 kW, respectively. What is the operating power of the motor?
    87.5%
    80.69%
    94.76%
    89.49%
    30s
  • Q5
    In a 13.8 kV, 10 MVA base three phase system a phase to phase fault occurs. If the Thevin's equivalent impedance of the system is 2.63%, what is the magnitude of the fault current?
    27,600 A
    7,970 A
    15,900 A
    13,800 A
    30s
  • Q6
    Consider a system with sequence impedances of Z1 = j0.2577 pu , Z2 = j0.2085 pu and Z0 = j0.14p, determine the fault current la1 for a single line to ground fault at A.
    -j3.67 pu
    -j1 pu
    -j2.13 pu
    -j1.65 pu
    30s
  • Q7
    A 150 MVA, 13.8 kV, Y-connected 3 ϕ, 60 Hz alternator is operating at rated voltage and at no-load when a three-phase fault occurs at its terminals. If the subtransient reactance of the alternator is j 02 p.u., calculate the current at the instant the fault occurs.
    18,117 A
    10,460 A
    6040 A
    31,380 A
    30s
  • Q8
    A 150-MVA, 13.8-KV, Y-connected, 3φ , 60-HZ alternator is operating at rated voltage and at no-load when a threephase faults occurs at its terminals. If the sub transient reactance of the alternators is j0.2 pu, calculate the current the instant the fault occurs.
    6276 amps
    10870 amps
    31380 amps
    32611 amps
    30s
  • Q9
    Power in a balanced 3-phase system is produced by two wattmeter method and it is found that the ratio of the two wattmeter readings is 2 is to 1. What is the power factor of the system?
    0.82
    0.866
    0.707
    0.9
    30s
  • Q10
    A 220 V, 3-phase, 4 wire abc system supplies unbalanced wye-connected resistances of Ra = 10 ohms, Rb = 15 ohms, and Rc = 20 ohms. Determine the total power of the system.
    3495 W
    3385 W
    3895 W
    3560 W
    30s
  • Q11
    A balanced delta connected load of (4 + j3) Ω per phase is connected to a three-phase, 230 V supply. Find the total kVA.
    25.39 kVA
    37.01 kVA
    31.74 kVA
    19.04 kVA
    30s
  • Q12
    A load of 10,000 kVA, 80% lagging is connected to a 13,200-volt line. How much capacitive reactive power is needed to correct the power factor to 97% lagging?
    3138 kVAR
    2547 kVAR
    3995 kVAR
    5156 kVAR
    30s
  • Q13
    A balanced delta connected load draws 100 A line current from a balanced 3 phase supply. Determine the zero sequence components of the currents.
    50 – j86.6
    86.6 + j50
    -50 – j86.6
    0
    30s
  • Q14
    In two-wattmeter method of power measurement, the reading of the two wattmeters were 6717 watts and 2658 watts, respectively. Find the power factor.
    0.80
    0.90
    0.60
    0.70
    30s
  • Q15
    A balanced delta connected load of 15 + j18 ohms per phase is connected at the end of a three-phase line. The line impedance is 1 + j2 ohms per phase.
    -7.2 – j9.6 A
    -7.2 + j9.6 A
    7.2 – j9.6 A
    7.2 + j9.6 A
    30s